Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2021, 05:27 AM
  • 18 0109_18 0108_05042021_224507.mp4

Date
05/04/2021
W/O
891398
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13929
Time
10:27 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8859
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0109
Downstream MH
18 0108
Dir. of Survey
Downstream
Length Surveyed
266.5 ft.
Total Length
266.5 ft.
Structural Index
3
Structural Quick
3K24
Structural Rating
185
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
185
Pipe schematic from manhole 18 0109 to 18 0108
MH: 18 0109MH: 18 0108downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01090 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK4.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES40 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"60.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES66.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES78.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES92 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES111.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES118 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES127.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES141.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES215.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES241.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.2 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES266.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0108266.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (12)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    23.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    60.5 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    66.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    78.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    102.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    111.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    118 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    127.2 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    203.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    215.9 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    249.2 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
266.5AMH18 0108
203.4CL
247.3TFC
60.5FL
0AMH18 0109
147.5TFC
266.5SAV
215.9CM
127.2FL
4.3SAV
102.9CL
46.2TFC
0MWL
189.8TF
0MWM
98.1TFC
266.5MGOCONNECTION AT THE MH 3 OC'LOCK
241.6TFC
78.4CL
141.1TF
66.2FL
118FL
0MGOCONNECTION AT THE MH 3 OC'LOCK
23.8FL
195.9TFC
249.2CM
111.9CL
40TF
92TF

Properties (7)

additional_info
630074050421201
custom_field_three
AGGREGATE VISIBLE/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-04T22:27:48-07:00
documentation
PROPIPE
is_lateral_inspection
false