Wastewater/Activity/PacpInspection/1.0May 5, 2021, 05:49 AM
  • 18 0108_18 0107_05042021_230543.mp4

Date
05/04/2021
W/O
891398
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13928
Time
10:49 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8859
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0108
Downstream MH
18 0107
Dir. of Survey
Downstream
Length Surveyed
272 ft.
Total Length
272 ft.
Structural Index
3
Structural Quick
3J27
Structural Rating
182
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
182
Pipe schematic from manhole 18 0108 to 18 0107
MH: 18 0108MH: 18 0107downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01080 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"43.9 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES61.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES65 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES78.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES117 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES130.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES156.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES172.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES179.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES228.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish271.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK272 ft. AMH - Downstream Manhole, Survey Ends - 18 0107

Observation photos (10)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    43.9 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    61.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    65 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    110.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    117 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    141.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    156.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    172.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    196.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
182.4TFC
228.3TF
156.9CL
271.9SAV
20.5TF
61.9CL
133.6TFC
272AMH18 0107
141.4CL
78.5TF
43.9FL
65CL
0AMH18 0108
2.4SAV
0MWM
271.9MGOCONNECTION AT THE MH 3 OC'LOCK
110.7CL
81.6TFC
23.6TFC
196.5FL
172.3CL
130.3TF
0MGOCONNECTION AT THE MH 3 OC'LOCK
179.4TF
0MWL
231.4TFC
117CL

Properties (7)

additional_info
630074050421201
custom_field_three
AGGREGATE VISIBLE/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-04T22:49:14-07:00
documentation
PROPIPE
is_lateral_inspection
false