Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2021, 08:40 AM
  • 08 0539_08 0538_612021_014520.mp4

Date
06/01/2021
W/O
0890878
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00601
Time
1:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1820
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210525MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0538
Downstream MH
08 0539
Dir. of Survey
Upstream
Length Surveyed
20.2 ft.
Total Length
20.2 ft.
Structural Index
2
Structural Quick
3125
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 08 0538 to 08 0539
MH: 08 0538MH: 08 0539upstream0 ft. AMH - Upstream Manhole, Survey Ends( INSPECTION COMPLETED BY REVERSE INSPECTION) - 1:50AM( INSPECTION COMPLETED BY REVERSE INSPECTION)0.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H0.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H4.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL8.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE8.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL12.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL16.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT20.2 ft. AMH - Downstream Manhole, Survey Begins - 1:40AM20.2 ft. MWM - Water Mark, 20 %of cross sectional area20.2 ft. MWL - Water Level, 10 %of cross sectional area

Observations (11)

DistanceCodeObservation
19.9FCH
11.8FLHAIRLINE
20.2AMH1:50AM( INSPECTION COMPLETED BY REVERSE INSPECTION)
0AMH1:40AM
19.9FLH
11.7FCSL
3.5FCSLIGHT
7.4FCSL
0MWM
0MWL
15.6FCSL

Properties (6)

custom_field_three
HAIRLINE LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2021-06-01T01:40:00-07:00
documentation
MARTIN,BARR,RAMIREZ
is_lateral_inspection
false