Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2021, 10:35 AM
  • 08 0539_08 0538_5252021_034616.mp4

Date
05/25/2021
W/O
0890878
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00601
Time
3:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1820
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210525MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0539
Downstream MH
08 0538
Dir. of Survey
Downstream
Length Surveyed
276.7 ft.
Total Length
276.7 ft.
Structural Index
2
Structural Quick
352B
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
41
Pipe schematic from manhole 08 0539 to 08 0538
MH: 08 0539MH: 08 0538downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM0 ft. MWL - Water Level, 5 %of cross sectional area3.3 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES - SLIGHT6.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL10.1 ft. MGO - General Observation - LIGHTS ON CAMERA OVERHEATED18.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL30.6 ft. FC - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES - SL79.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL83.9 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - H83.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H87.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL100.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H104.4 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL104.4 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL108.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL108.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL112.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS112.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS112.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS112.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS259.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE260.1 ft. MGO - General Observation - ZOOM 16' OUT OF CCTV CABLE268.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE(2 PIPE SECTIONS LONG)276.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE AT JOINTS276.1 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS276.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% SLIGHT AT JOINTS276.1 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% HAIRLINE AT JOINTS276.7 ft. AMH - Downstream Manhole, Survey Ends - 4:40AM

Observation photos (2)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    259.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • General Observation - ZOOM 16' OUT OF CCTV CABLE

    260.1 ft. - General Observation - ZOOM 16' OUT OF CCTV CABLE

Observations (29)

DistanceCodeObservation
260.1MGOZOOM 16' OUT OF CCTV CABLE
79.7FCSL
100.2FCH
0MWM
268.1FLHAIRLINE(2 PIPE SECTIONS LONG)
276.1FC50% HAIRLINE AT JOINTS
83.9FLH
6.2FCSL
104.4FCSL
0AMH3:40AM
30.6FCSL
10.1MGOLIGHTS ON CAMERA OVERHEATED
108.4FCSL
259.7FLHAIRLINE
276.1FL10% SLIGHT AT JOINTS
276.1FC40% SLIGHT AT JOINTS
0MWL
276.1FL10% HAIRLINE AT JOINTS
112.6FCHAIRLINE AT JOINTS
18.4FCSL
108.4FCSL
276.7AMH4:40AM
83.9FLH
112.6FCSLIGHT AT JOINTS
104.4FCSL
112.6FLHAIRLINE AT JOINTS
112.6FLSLIGHT AT JOINTS
3.3FCSLIGHT
87.9FCSL

Properties (6)

custom_field_three
HAIRLINE FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2021-05-25T03:35:00-07:00
documentation
MARTIN,OLIVER 111,RUVALCABA,BARR
is_lateral_inspection
false