Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2021, 07:59 PM
  • D 0087_D 0086_5272021_132700.mp4

Date
05/27/2021
W/O
0890933
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00155
PipeID
P09987
Time
12:59 PM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1824
Sewer Name
D JOINT OUTFALL D - UNIT 5
City
GARDENA
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20210527SHO_JOINT_OUTFALL_D_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
D 0087
Downstream MH
D 0086
Dir. of Survey
Downstream
Length Surveyed
299.9 ft.
Total Length
299.9 ft.
Structural Index
4
Structural Quick
5331
Structural Rating
20
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
20
Pipe schematic from manhole D 0087 to D 0086
MH: D 0087MH: D 0086downstream0 ft. AMH - Upstream Manhole, Survey Begins - D 870 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area4.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start4.6 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start70.6 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES181.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"185.1 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES294.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start298.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish298.9 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish299 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish299.9 ft. AMH - Downstream Manhole, Survey Ends - D 86

Observations (13)

DistanceCodeObservation
0AMHD 87
181.3TF
70.6SRV
294.3SRV
4.6SSS
299.9AMHD 86
4.6SAV
298.9SSS
185.1SRV
0MWM
299SRV
298.9SAV
0MWL

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2021-05-27T12:59:05-07:00
documentation
OBREGON, IGNACIO, RAMIREZ, CASTILLO
is_lateral_inspection
false