Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2021, 05:21 PM
  • D 0089_D 0088_5272021_112256.mp4

Date
05/27/2021
W/O
0890933
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00155
PipeID
P09989
Time
10:21 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1824
Sewer Name
D JOINT OUTFALL D - UNIT 5
City
GARDENA
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20210527SHO_JOINT_OUTFALL_D_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
D 0089
Downstream MH
D 0088
Dir. of Survey
Downstream
Length Surveyed
463.4 ft.
Total Length
463.4 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole D 0089 to D 0088
MH: D 0089MH: D 0088downstream0 ft. AMH - Upstream Manhole, Survey Begins - D 890 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area9 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start13.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start24 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish43.3 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES93 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start459.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish459.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish463.4 ft. AMH - Downstream Manhole, Survey Ends - D 88

Observation photos (1)

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    13.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
9SAV
463.4AMHD 88
13.8SRV
0AMHD 89
24SRV
0MWL
93SSS
459.1SSS
0MWM
43.3SRV
459.1SAV

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2021-05-27T10:21:33-07:00
documentation
OBREGON, IGNACIO, RAMIREZ, CASTILLO
is_lateral_inspection