Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2021, 11:09 AM
  • 01 0557_E 0063_05142021_041412.mp4

Date
05/14/2021
W/O
891399
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00194
PipeID
P02166
Time
4:09 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8909
Sewer Name
01 ALAMEDA STREET EXTENSION TRUNK
City
LYNWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_891399_TV01284_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
15 in.
Upstream MH
E 0063
Downstream MH
01 0557
Dir. of Survey
Upstream
Length Surveyed
29.7 ft.
Total Length
29.7 ft.
Structural Index
3
Structural Quick
3500
Structural Rating
15
O&M Index
2
O&M Quick
3126
O&M Rating
15
Overall Index
3
Overall Quick
Overall Rating
30
Pipe schematic from manhole E 0063 to 01 0557
MH: E 0063MH: 01 0557upstream0 ft. MSA - Survey Abandoned - REVERSAL COMPLETE. REMAINDER COMPLETED FROM U/S MH.0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish6 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES18.8 ft. MGO - General Observation - MAG COAT24.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start29.7 ft. MWM - Water Mark, 20 %of cross sectional area29.7 ft. AMH - Downstream Manhole, Survey Begins - E 006329.7 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    10.9 ft. - General Observation - MAG COAT

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 05 o'clock,  , within 8 inches of joint: YES

    23.7 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES

  • Survey Abandoned - REVERSAL COMPLETE. REMAINDER COMPLETED FROM U/S MH.

    29.7 ft. - Survey Abandoned - REVERSAL COMPLETE. REMAINDER COMPLETED FROM U/S MH.

Observations (10)

DistanceCodeObservation
29.7MSAREVERSAL COMPLETE. REMAINDER COMPLETED FROM U/S MH.
2DAGS
0MWM
10.9MGOMAG COAT
29.7SAP
0AMHE 0063
29.7DAGS
23.7DAGS
0MWL
5.2SAP

Properties (7)

additional_info
630069051321201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-05-14T04:09:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false