Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2021, 09:56 AM
  • 18 0281_18 0280_05132021_031412.mp4

Date
05/13/2021
W/O
891121
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00702
PipeID
P14109
Time
2:56 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8865
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_891121_TV18178_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0281
Downstream MH
18 0280
Dir. of Survey
Downstream
Length Surveyed
345 ft.
Total Length
345 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
340
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
342
Pipe schematic from manhole 18 0281 to 18 0280
MH: 18 0281MH: 18 0280downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02810 ft. MWM - Water Mark, 25 %of cross sectional area3.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. MGO - General Observation - 55% MAG COAT18.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"21.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN142.6 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN165.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"214 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"217.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"266 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"269 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"319.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN331 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock - STICK/RAGS345 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345 ft. AMH - Downstream Manhole, Survey Ends - 18 0280

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    142.6 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (24)

DistanceCodeObservation
266TFC
69.7TFC
345SAV
319.6TFOPEN
3.1SSS
331OBZSTICK/RAGS
0MWL
118.6TFOPEN
214TFC
18.5TFC
165.9TFC
217.2TFC
168.9TFC
72.4TFC
269TFC
345SSS
3.1SAV
21.5TFC
3.1MGO55% MAG COAT
0AMH18 0281
142.6TSOPEN
0MWM
316.1TFC
345AMH18 0280

Properties (7)

additional_info
630138051221203
custom_field_three
AGGREGATE VISIBLE/SPALLING
custom_field_two
3
customer
1
datetime
2021-05-13T02:56:29-07:00
documentation
PROPIPE
is_lateral_inspection
false