Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2021, 10:15 AM
  • 32 1191_32 1190_05102021_032657.mp4

Date
05/10/2021
W/O
891131
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00843
PipeID
P19645
Time
3:15 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8904
Sewer Name
32 SOLEDAD CANYON RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_891131_TV32050_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
32 1191
Downstream MH
32 1190
Dir. of Survey
Downstream
Length Surveyed
123.3 ft.
Total Length
123.3 ft.
Structural Index
3
Structural Quick
5939
Structural Rating
102
O&M Index
3
O&M Quick
413D
O&M Rating
121
Overall Index
3
Overall Quick
Overall Rating
223
Pipe schematic from manhole 32 1191 to 32 1190
MH: 32 1191MH: 32 1190downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 11912 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start8 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS UNDER WATER45.8 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start75.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start83.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start93.5 ft. HSV - Hole Soil Visible, from 09 to 12 o'clock, within 8 inches of joint: YES - IN OLDER VIDEOS, LOOKS LIKE A PATCHED HOLE WHICH PRESENTLY MAY BE COVERED WITH GREASE, ETC...121.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish121.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish121.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish121.3 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish121.3 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish123.3 ft. AMH - Downstream Manhole, Survey Ends - 32 1190

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    45.8 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    75.8 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    83.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Hole Soil Visible, from 09 to 12 o'clock, within 8 inches of joint: YES - IN OLDER VIDEOS, LOOKS LIKE A PATCHED HOLE WHICH PRESENTLY MAY BE COVERED WITH GREASE, ETC...

    93.5 ft. - Hole Soil Visible, from 09 to 12 o'clock, within 8 inches of joint: YES - IN OLDER VIDEOS, LOOKS LIKE A PATCHED HOLE WHICH PRESENTLY MAY BE COVERED WITH GREASE, ETC...

Observations (16)

DistanceCodeObservation
0MWL
123.3AMH32 1190
8DSZDEBRIS UNDER WATER
121.3DAGS
0MGOCONNECTION AT MH 3 O'CLOCK
0MWM
121.3SAP
75.8SAP
45.8SSS
2DAGS
121.3SRV
83.1SRV
121.3DSZ
0AMH32 1191
93.5HSVIN OLDER VIDEOS, LOOKS LIKE A PATCHED HOLE WHICH PRESENTLY MAY BE COVERED WITH GREASE, ETC...
121.3SSS

Properties (8)

additional_info
630069051021001
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-05-10T03:15:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26872