Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 23, 2021, 06:06 AM
  • 22 0495_22 0494_04222021_231621.mp4

Date
04/22/2021
W/O
886009
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00800
PipeID
P16834
Time
11:06 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8743
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_886009_TV22031_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
22 0495
Downstream MH
22 0494
Dir. of Survey
Downstream
Length Surveyed
167.6 ft.
Total Length
167.6 ft.
Structural Index
3
Structural Quick
3L2F
Structural Rating
258
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
324
Pipe schematic from manhole 22 0495 to 22 0494
MH: 22 0495MH: 22 0494downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 04950 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 25% MAG COAT3.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start25.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"165 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish165 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0494167.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish167.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
3.5SAV
167.6SAV
28.9TFC
167.6AMH22 0494
2SSS
0AMH22 0495
2DAGS
165DAGS
25.8TFC
0MWL
2MGO25% MAG COAT
167.6CM
12.5CM
0MWM
77.4TFC
165SSS
167.6MGOCONN @ MH 3 O'CLOCK/ACTIVE
131.3TFC
128TFC
80.1TFC

Properties (7)

additional_info
630074042221201
custom_field_three
AGGREGATE VISIBLE/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-04-22T23:06:55-07:00
documentation
PROPIPE
is_lateral_inspection
false