Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2021, 07:36 AM
  • 21 0515_21 0514_05132021_005535.mp4

Date
05/13/2021
W/O
890874
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00779
PipeID
P15726
Time
12:36 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8952
Sewer Name
21 PHILLIPS BOULEVARD TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_890874_TV21107_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
21 0515
Downstream MH
21 0514
Dir. of Survey
Downstream
Length Surveyed
555.5 ft.
Total Length
555.5 ft.
Structural Index
3
Structural Quick
3U2U
Structural Rating
550
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
550
Pipe schematic from manhole 21 0515 to 21 0514
MH: 21 0515MH: 21 0514downstream0 ft. AMH - Upstream Manhole, Survey Begins - 21 05150 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. MGO - General Observation - MAG COAT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start131.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"238.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"300.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8" - DEBRIS341.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8" - ACTIVE424.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"554.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish554.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish555.5 ft. AMH - Downstream Manhole, Survey Ends - 21 0514

Observation photos (8)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    131.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    238.1 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8" - DEBRIS

    300.1 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8" - DEBRIS

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8" - ACTIVE

    341.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8" - ACTIVE

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    424.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

Observations (14)

DistanceCodeObservation
300.1TBDEBRIS
2MGOMAG COAT
0AMH21 0515
0MWL
238.1TB
0MWM
424.4TB
555.5AMH21 0514
341.6TBACTIVE
2SAV
131.4TB
554.3SAV
554.3SSS
2SSS

Properties (6)

custom_field_three
SPALLING. AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-13T00:36:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false