Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2021, 07:32 AM
  • 14 0080_14 0079_04092021_004704.mp4

Date
04/09/2021
W/O
886341
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00577
PipeID
P18094
Time
12:32 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8774
Sewer Name
14 TRUNK "A"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_886341_TV14039_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
14 0080
Downstream MH
14 0079
Dir. of Survey
Downstream
Length Surveyed
448.1 ft.
Total Length
448.1 ft.
Structural Index
3
Structural Quick
5Q3Q
Structural Rating
890
O&M Index
2
O&M Quick
412Q
O&M Rating
182
Overall Index
3
Overall Quick
Overall Rating
1072
Pipe schematic from manhole 14 0080 to 14 0079
MH: 14 0080MH: 14 0079downstream0 ft. MGO - General Observation - CONN @ MH 6 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 14 00800 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 55% MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start446.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish446.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish446.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish446.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish448.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0079

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
446.3SSS
446.3SAP
446.3DAGS
0MGOCONN @ MH 6 O'CLOCK/ACTIVE
2SSS
2SRV
448.1AMH14 0079
0AMH14 0080
0MWM
2MGO55% MAG COAT
2SAP
0DAGS
446.3SRV
0MWL

Properties (7)

additional_info
630069040821201
custom_field_three
PROJECTING AGGREGATE/VISIBLE REINFORCEMENT
custom_field_two
2
customer
1
datetime
2021-04-09T00:32:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false