Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2021, 08:32 AM
  • 14 0435_14 0434_05042021_014933.mp4

Date
05/04/2021
W/O
890935
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00578
PipeID
P18520
Time
1:32 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8798
Sewer Name
14 TRUNK "B"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_890935_TV14019_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0434
Downstream MH
14 0435
Dir. of Survey
Upstream
Length Surveyed
375.9 ft.
Total Length
375.9 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
370
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
370
Pipe schematic from manhole 14 0434 to 14 0435
MH: 14 0434MH: 14 0435upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 0435, ABANDONED MH.1.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish39.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"67.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"241.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"267 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"290.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"319.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"343.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"373.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start373.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start375.9 ft. MWL - Water Level, 40 %of cross sectional area375.9 ft. MWM - Water Mark, 40 %of cross sectional area375.9 ft. AMH - Downstream Manhole, Survey Begins - 14 0434

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Upstream Manhole, Survey Ends - 14 0435, ABANDONED MH.

    375.9 ft. - Upstream Manhole, Survey Ends - 14 0435, ABANDONED MH.

Observations (20)

DistanceCodeObservation
2SAP
336.7TFC
56.5TFC
85.7TFC
284.6TFC
0MWL
235.9TFC
32.8TFC
158.6TFC
108.9TFC
374.3SAP
0MWM
134.2TFC
0AMH14 0434
375.9AMH14 0435, ABANDONED MH.
2SSS
374.3SSS
260TFC
211.1TFC
308.4TFC

Properties (7)

additional_info
630069050321201
custom_field_three
SPALLING/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-05-04T01:32:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false