Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 18, 2017, 05:22 AM
  • J 0474_J 0473 _07172017_222351.mp4

Date
07/17/2017
W/O
624549
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01108
PipeID
P22769
Time
10:22 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4710
Sewer Name
J JOINT OUTFALL J - UNIT 1A REPLACEMENT
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
WO_624549_TV05241_JUN2017
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
J 0474
Downstream MH
J 0473
Dir. of Survey
Downstream
Length Surveyed
34.1 ft.
Total Length
34.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2600
O&M Rating
12
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole J 0474 to J 0473
MH: J 0474MH: J 0473downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 04742 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start34.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish34.1 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    34.1 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

Observations (6)

DistanceCodeObservation
34.1DAGS
0MWM
2DAGS
0MWL
0AMHJ 0474
34.1MSAVIEW OF DOWNLEG OF U/S SIPHON.

Properties (7)

additional_info
SC345443
custom_field_two
4
customer
LACSD
datetime
2017-07-17T22:22:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
36558