Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2017, 10:42 AM
  • J 0466_J 0465 _07202017_034601.mp4

Date
07/20/2017
W/O
624549
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01108
PipeID
P22761
Time
3:42 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4714
Sewer Name
J JOINT OUTFALL J - UNIT 1A REPLACEMENT
City
HARBOR CITY
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
WO_624549_TV05241_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
J 0466
Downstream MH
J 0465
Dir. of Survey
Downstream
Length Surveyed
237.1 ft.
Total Length
237.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
98
Overall Index
2
Overall Quick
Overall Rating
98
Pipe schematic from manhole J 0466 to J 0465
MH: J 0466MH: J 0465downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 04660 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start39.2 ft. ISZ - Intruding Sealing Other, 5 %of cross sectional area, from 12 to 02 o'clock87.4 ft. ISZ - Intruding Sealing Other, 5 %of cross sectional area, from 01 to 04 o'clock237.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish237.1 ft. AMH - Downstream Manhole, Survey Ends - J 0465

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Intruding Sealing Other, 5 %of cross sectional area, from 12 to 02 o'clock

    39.2 ft. - Intruding Sealing Other, 5 %of cross sectional area, from 12 to 02 o'clock

  • Intruding Sealing Other, 5 %of cross sectional area, from 01 to 04 o'clock

    87.4 ft. - Intruding Sealing Other, 5 %of cross sectional area, from 01 to 04 o'clock

Observations (8)

DistanceCodeObservation
0MWM
39.2ISZ
87.4ISZ
0AMHJ 0466
237.1DAGS
2DAGS
0MWL
237.1AMHJ 0465

Properties (7)

additional_info
SC345447
custom_field_two
4
customer
LACSD
datetime
2017-07-20T03:42:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
36558