- Date
- 05/03/2021
- W/O
- 890798
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00849
- PipeID
- P23770
- Time
- 11:14 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8855
- Sewer Name
- 29 SIGNAL HILL OUTFALL TRUNK
- City
- LONG BEACH
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 03
- Page No.
- 19
- Purpose
- Routine Assessment
- Project
- WO_890798_TV29087_MAY2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 29 0002
- Downstream MH
- C 0590
- Dir. of Survey
- Downstream
- Length Surveyed
- 26 ft.
- Total Length
- 26 ft.
- Structural Index
- 3
- Structural Quick
- 5134
- Structural Rating
- 25
- O&M Index
- 3
- O&M Quick
- 3300
- O&M Rating
- 9
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 34
Pipe schematic from manhole 29 0002 to C 0590 Observation photos (5)

3.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

3.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

7.5 ft. - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

21.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

21.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES