Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 22, 2021, 08:36 AM
  • 15 1148_15 1184_04222021_014127.mp4

Date
04/22/2021
W/O
885831
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01185
PipeID
P26112
Time
1:36 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8786
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTION 2 RELIEF EXTENSION
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
02
Purpose
Routine Assessment
Project
WO_885831_TV15115_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 1148
Downstream MH
15 1184
Dir. of Survey
Downstream
Length Surveyed
66.6 ft.
Total Length
66.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2A00
O&M Rating
24
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 15 1148 to 15 1184
MH: 15 1148MH: 15 1184downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 11480 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start64.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish66.6 ft. AMH - Downstream Manhole, Survey Ends - 15 1184

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0MWL
64.4DAGS
2DAGS
0AMH15 1148
0MWM
66.6AMH15 1184

Properties (8)

additional_info
630069042121202
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-04-22T01:36:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39867