Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 22, 2021, 04:32 AM
  • 15 0596_15 0595_04212021_214626.mp4

Date
04/21/2021
W/O
885853
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00628
PipeID
P12528
Time
9:32 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8785
Sewer Name
15 SANTA ANITA CONNECTION TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_885853_TV15086_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0596
Downstream MH
15 0595
Dir. of Survey
Downstream
Length Surveyed
435.2 ft.
Total Length
435.2 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
2
O&M Quick
2P00
O&M Rating
172
Overall Index
2
Overall Quick
Overall Rating
181
Pipe schematic from manhole 15 0596 to 15 0595
MH: 15 0596MH: 15 0595downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 05960 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start38.5 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES172.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES326.1 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES345.3 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"405.9 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"415.1 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES433.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish435.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0595

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    38.5 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    172.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    326.1 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    415.1 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
0MWL
415.1CS
38.5CM
0AMH15 0596
2DAGS
405.9TFA
435.2AMH15 0595
326.1CS
433.2DAGS
172.7CL
345.3TFA
0MWM

Properties (7)

additional_info
630069042121201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-04-21T21:32:05-07:00
documentation
PRO PIPE
is_lateral_inspection
false