Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 22, 2021, 05:17 AM
  • 15 0594_15 0593_04212021_223008.mp4

Date
04/21/2021
W/O
885853
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00628
PipeID
P12526
Time
10:17 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8785
Sewer Name
15 SANTA ANITA CONNECTION TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_885853_TV15086_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0594
Downstream MH
15 0593
Dir. of Survey
Downstream
Length Surveyed
390.2 ft.
Total Length
390.2 ft.
Structural Index
2
Structural Quick
2800
Structural Rating
16
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
170
Pipe schematic from manhole 15 0594 to 15 0593
MH: 15 0594MH: 15 0593downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 05940 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start93.3 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start116.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish202.4 ft. CS - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES252.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES311.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"333.6 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES388.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish390.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0593

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

    93.3 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    202.4 ft. - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    298.4 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
311.3TFC
0MWM
0AMH15 0594
333.6CL
116.5CL
252.6TFC
388.1DAGS
202.4CS
93.3CL
298.4CL
390.2AMH15 0593
0MWL
2DAGS

Properties (7)

additional_info
630069042121201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-04-21T22:17:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false