Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 22, 2021, 06:12 AM
  • 15 0593_15 0592_04212021_232504.mp4

Date
04/21/2021
W/O
885853
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00628
PipeID
P12525
Time
11:12 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8785
Sewer Name
15 SANTA ANITA CONNECTION TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_885853_TV15086_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0593
Downstream MH
15 0592
Dir. of Survey
Downstream
Length Surveyed
312.2 ft.
Total Length
312.2 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
312L
O&M Rating
129
Overall Index
2
Overall Quick
Overall Rating
138
Pipe schematic from manhole 15 0593 to 15 0592
MH: 15 0593MH: 15 0592downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 05930 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start105.6 ft. RTJ - Roots Tap Joint, at 08 o'clock, 5 %, within 8 inches of joint: YESR105.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES106.8 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES180.9 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES298.4 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES309.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish312.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE312.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0592

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Roots Tap Joint, at 08 o'clock, 5 %, within 8 inches of joint: YESR

    105.6 ft. - Roots Tap Joint, at 08 o'clock, 5 %, within 8 inches of joint: YESR

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    105.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 15 %of cross sectional area, from 09 to 11 o'clock,  , within 8 inches of joint: YES

    106.8 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    180.9 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    298.4 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    312.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
0MWL
298.4CM
309.9DAGS
0AMH15 0593
180.9CM
106.8DAGS
105.6RTJ
0MWM
105.6CM
312.2MGOCOCKROACHES IN MANHOLE
312.2AMH15 0592
2DAGS

Properties (7)

additional_info
630069042121201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-04-21T23:12:55-07:00
documentation
PRO PIPE
is_lateral_inspection
false