Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2021, 08:01 AM
  • C 0377_C 0376_04152021_012147.mp4

Date
04/15/2021
W/O
886146
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00141
PipeID
P09840
Time
1:01 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8729
Sewer Name
C JOINT OUTFALL C - UNIT 8C
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_886146_TV19080_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
78 in.
Upstream MH
C 0377
Downstream MH
C 0376
Dir. of Survey
Downstream
Length Surveyed
638.9 ft.
Total Length
638.9 ft.
Structural Index
3
Structural Quick
3X00
Structural Rating
381
O&M Index
4
O&M Quick
4533
O&M Rating
29
Overall Index
3
Overall Quick
Overall Rating
410
Pipe schematic from manhole C 0377 to C 0376
MH: C 0377MH: C 0376downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03770 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. MGO - General Observation - MAG COAT145.5 ft. IR - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES226.1 ft. IR - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES274.4 ft. IR - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES539.2 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES555.5 ft. ID - Infiltration Dripper, from 01 to 02 o'clock, within 8 inches of joint: YES612.2 ft. IR - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES622.8 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES630.4 ft. IR - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES638.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK638.9 ft. AMH - Downstream Manhole, Survey Ends - C 0376638.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

    145.5 ft. - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

    226.1 ft. - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

    274.4 ft. - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    539.2 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 01 to 02 o'clock, within 8 inches of joint: YES

    555.5 ft. - Infiltration Dripper, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

    612.2 ft. - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES

    622.8 ft. - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

    630.4 ft. - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
539.2ID
0AMHC 0377
622.8ID
638.9MGOCONNECTION AT THE MH 3 OC'LOCK
612.2IR
638.9AMHC 0376
3SAP
145.5IR
274.4IR
0MWM
3MGOMAG COAT
0MWL
638.9SAP
555.5ID
630.4IR
226.1IR

Properties (8)

additional_info
630074041421202
custom_field_three
AGGREGATE PROJECTING/INFILTRATION
custom_field_two
3
customer
1
datetime
2021-04-15T01:01:20-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26760