Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2021, 05:41 AM
  • 29 0005_29 0004_05032021_224942.mp4

Date
05/03/2021
W/O
891048
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00849
PipeID
P17679
Time
10:41 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8856
Sewer Name
29 SIGNAL HILL OUTFALL TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_891048_TV29096_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
29 0005
Downstream MH
29 0004
Dir. of Survey
Downstream
Length Surveyed
91.8 ft.
Total Length
91.8 ft.
Structural Index
4
Structural Quick
5B3B
Structural Rating
136
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
139
Pipe schematic from manhole 29 0005 to 29 0004
MH: 29 0005MH: 29 0004downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 00050 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2.2 ft. MGO - General Observation - MAG COAT2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start19.2 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish89.2 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish89.2 ft. ID - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: NO89.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish91.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0004

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    19.2 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: NO

    89.2 ft. - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: NO

Observations (13)

DistanceCodeObservation
19.2IS
0AMH29 0005
3.2SRV
0MWL
89.2IS
2.2MGOMAG COAT
2.2SAP
0MGOCONNECTION AT THE MH 3 OC'LOCK
91.8AMH29 0004
89.1SAP
0MWM
89.2ID
89.2SRV

Properties (7)

additional_info
630074050321202
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-05-03T22:41:32-07:00
documentation
PROPIPE
is_lateral_inspection
false