Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 16, 2021, 05:34 AM
  • B 1499_B 1098_04152021_225838.mp4

Date
04/15/2021
W/O
886019
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01124
PipeID
P13724
Time
10:34 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8731
Sewer Name
B JOINT OUTFALL B - UNIT 6G
City
ALHAMBRA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_886019_TV16101_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
B 1499
Downstream MH
B 1098
Dir. of Survey
Downstream
Length Surveyed
464.8 ft.
Total Length
464.8 ft.
Structural Index
4
Structural Quick
5R3R
Structural Rating
744
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
744
Pipe schematic from manhole B 1499 to B 1098
MH: B 1499MH: B 1098downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 14990 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start136.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"464.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish464.8 ft. AMH - Downstream Manhole, Survey Ends - B 1098464.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2.2SRV
0MWL
0AMHB 1499
464.8SRV
0MWM
464.8AMHB 1098
464.8SAP
0MGOCONNECTION AT THE MH 9 OC'LOCK
2.1SAP
136.1TF

Properties (7)

additional_info
630074041521202
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2021-04-15T22:34:00-07:00
documentation
PROPIPE
is_lateral_inspection
false