Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2021, 10:44 AM
  • 01 1285_01 1284_04212021_041110.mp4

Date
04/21/2021
W/O
871885
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00207
PipeID
P01581
Time
3:44 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8737
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE RELIEF TRUNK
City
los angeles
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
CA_WO_871885
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
15 in.
Upstream MH
01 1284
Downstream MH
01 1285
Dir. of Survey
Upstream
Length Surveyed
537.9 ft.
Total Length
537.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3R00
O&M Rating
282
Overall Index
3
Overall Quick
Overall Rating
282
Pipe schematic from manhole 01 1284 to 01 1285
MH: 01 1284MH: 01 1285upstream0 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 01 128513.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"53.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"70 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"212.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"256.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"292.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"327 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"374.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"404.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"423.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"467.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"471.8 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO, Start - sludge537.9 ft. MWL - Water Level, 15 %of cross sectional area537.9 ft. AMH - Downstream Manhole, Survey Begins - 01 1284537.9 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (3)

  • Deposits Settled Other,  20 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: NO, Start - sludge

    66.1 ft. - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO, Start - sludge

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    362.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    484.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (21)

DistanceCodeObservation
348TF
66.1DSZsludge
245.1TF
114.3TF
325TF
0MWL
524.3TF
467.9TF
70.5TFA
133.8TF
210.9TF
448.4TF
281.1TF
0AMH01 1284
484.3TB
163.7TF
537.9DSZ
537.9AMH01 1285
0MWM
362.8TB
393.7TF

Properties (7)

additional_info
630074041921203
custom_field_three
no severe defects
custom_field_two
4
customer
1
datetime
2021-04-21T03:44:49-07:00
documentation
PROPIPE
is_lateral_inspection
false