Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2021, 08:55 AM
  • J 0223_J 033A_5132021_020102.mp4

Date
05/13/2021
W/O
0879983
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11469
Time
1:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1804
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47
Purpose
Capital Improvement Program Assesment
Project
20210511MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0223
Downstream MH
J 0222A
Dir. of Survey
Downstream
Length Surveyed
411.7 ft.
Total Length
411.7 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole J 0223 to J 0222A
MH: J 0223MH: J 0222Adownstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:00AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE20.1 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCKS116.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE175.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, - SEVERE AGG VERY SPORATIC210.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE338.1 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCKS411.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE411.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active411.7 ft. AMH - Downstream Manhole, Survey Ends - 2:25AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    116.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO,  - SEVERE AGG VERY SPORATIC

    175.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, - SEVERE AGG VERY SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    210.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

Observations (12)

DistanceCodeObservation
411.7AMH2:25AM
0MWM
338.1DSZROCKS
411.4SSSBLISTERING PEELING CONCRETE
0MWL
210.2SSSPEELING CONCRETE
20.1DSZROCKS
411.4MGOConn. @ Mh, 3 O' Clock. Active
175.1SAVSEVERE AGG VERY SPORATIC
116.9SSSBLISTERING PEELING CONCRETE
2SSSBLISTERING PEELING CONCRETE
0AMH2:00AM

Properties (6)

custom_field_three
SEVERE AGG VISIBLE
custom_field_two
3
customer
LACSD
datetime
2021-05-13T01:55:00-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,BARR
is_lateral_inspection
false