Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2015, 08:36 AM
  • 14 0007_14 0006_20151119_014104.mp4

Date
11/19/2015
W/O
525158
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00576
PipeID
P18019
Time
12:36 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2833
Sewer Name
14 ROSAMOND OUTFALL TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
01
Purpose
Routine Assessment
Project
WO_525158_TV14016_SEPT2015
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
14 0007
Downstream MH
14 0006
Dir. of Survey
Downstream
Length Surveyed
648.9 ft.
Total Length
648.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Y00
O&M Rating
258
Overall Index
2
Overall Quick
Overall Rating
258
Pipe schematic from manhole 14 0007 to 14 0006
MH: 14 0007MH: 14 0006downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 00070 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start648.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish648.9 ft. AMH - Downstream Manhole, Survey Ends - 14 0006

Observations (6)

DistanceCodeObservation
648.9DAGS
0AMH14 0007
0MWL
2DAGS
0MWM
648.9AMH14 0006

Properties (8)

additional_info
SC204168
custom_field_two
4
customer
LACSD
datetime
2015-11-19T00:36:03-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
PEP
year_laid
19910726