Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2016, 11:28 AM
  • 02 0105_02 0105_110216_044247.mp4

Date
11/02/2016
W/O
602602
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00237
PipeID
P02272
Time
4:28 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3754
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_602602_TV02019_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0105
Downstream MH
02 0104
Dir. of Survey
Downstream
Length Surveyed
299 ft.
Total Length
299 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
171
O&M Index
2
O&M Quick
2K11
O&M Rating
117
Overall Index
2
Overall Quick
Overall Rating
288
Pipe schematic from manhole 02 0105 to 02 0104
MH: 02 0105MH: 02 0104downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01050 ft. MWM - Water Mark, 40 %of cross sectional area7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start10.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start63.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"102 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"104.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"143.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"160.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"208.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"211.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"227.4 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES231.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"234.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"291.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"296.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish296.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish299 ft. AMH - Downstream Manhole, Survey Ends - 02 0104

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

    227.4 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
211.1TF
296.4DAGS
0MWL
102TF
143.3TF
160.9TFA
7DAGS
291.3TFA
227.4RFJ
296.4CM
10.3CM
104.6TFA
299AMH02 0104
234.7TFA
231.7TFA
0AMH02 0105
208.9TFC
0MWM
63.4TFC

Properties (6)

additional_info
SC303746
custom_field_two
3
customer
LACSD
datetime
2016-11-02T04:28:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false