Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2016, 11:53 AM
  • 02 0114_02 0114_110216_045523.mp4

Date
11/02/2016
W/O
602602
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00237
PipeID
P02281
Time
4:53 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3754
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER, CA
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_602602_TV02019_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0114
Downstream MH
02 0113
Dir. of Survey
Downstream
Length Surveyed
12.1 ft.
Total Length
12.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 0114 to 02 0113
MH: 02 0114MH: 02 0113downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 01140 ft. MWL - Water Level, 5 %of cross sectional area0.1 ft. MWM - Water Mark, 10 %of cross sectional area12.2 ft. MSA - Survey Abandoned - DUE TO ENCRUSTATION AT JOINT12.2 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 07 to 11 o'clock, , within 8 inches of joint: YES

Observation photos (2)

  • Survey Abandoned - DUE TO ENCRUSTATION AT JOINT

    12.2 ft. - Survey Abandoned - DUE TO ENCRUSTATION AT JOINT

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 07 to 11 o'clock,  , within 8 inches of joint: YES

    12.2 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 07 to 11 o'clock, , within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
0.1MWM
12.2MSADUE TO ENCRUSTATION AT JOINT
0AMH02 0114
0MWL
12.2DAE

Properties (6)

additional_info
SC303746
custom_field_two
4
customer
LACSD
datetime
2016-11-02T04:53:49-07:00
documentation
PRO-PIPE
is_lateral_inspection
false