Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2016, 10:51 AM
  • 02 1806_02 1541_14112016_025227.mp4

Date
11/14/2016
W/O
602593
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00236
PipeID
P04153
Time
2:51 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3822
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_602593_TV02018_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1806
Downstream MH
02 1541
Dir. of Survey
Downstream
Length Surveyed
110.6 ft.
Total Length
110.6 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1806 to 02 1541
MH: 02 1806MH: 02 1541downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 18062.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES48.8 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES68.5 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES110.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK110.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1541

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock,  , within 8 inches of joint: YES

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    48.8 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    68.5 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
48.8CM
0MWM
2.7DAGS
68.5CM
0MWL
110.6MGOCONNECTION AT MH 3 O'CLOCK
110.6AMH02 1541
0AMH02 1806

Properties (6)

additional_info
SC304571
custom_field_two
4
customer
LACSD
datetime
2016-11-14T02:51:50-08:00
documentation
PROPIPE
is_lateral_inspection
false