Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2016, 08:58 AM
  • 02 1644_02 1643_09112016_010103.mp4

Date
11/09/2016
W/O
602593
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00235
PipeID
P04078
Time
12:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3820
Sewer Name
02 ATLANTIC AVENUE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_602593_TV02018_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1644
Downstream MH
02 1643
Dir. of Survey
Downstream
Length Surveyed
303.8 ft.
Total Length
303.8 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
182
O&M Index
2
O&M Quick
4112
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
188
Pipe schematic from manhole 02 1644 to 02 1643
MH: 02 1644MH: 02 1643downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 16440 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area6.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"79 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.6 ft. RFJ - Roots Fine Joint, at 11 o'clock, within 8 inches of joint: YES246 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"253 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES262.5 ft. RFJ - Roots Fine Joint, from 12 to 02 o'clock, within 8 inches of joint: YES285.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.8 ft. AMH - Downstream Manhole, Survey Ends - 02 1643303.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    81.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Joint, at 11 o'clock, within 8 inches of joint: YES

    215.6 ft. - Roots Fine Joint, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

    253 ft. - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 12 to 02 o'clock, within 8 inches of joint: YES

    262.5 ft. - Roots Fine Joint, from 12 to 02 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
303.8AMH02 1643
0AMH02 1644
118.4TFC
262.5RFJ
285.3TFA
6.1CM
81.4TB
246TFC
0MWL
215.6RFJ
203.3TF
0MWM
36.8TFC
79TFC
303.8CM
160.9TFC
253FC

Properties (6)

additional_info
SC304569
custom_field_two
3
customer
LACSD
datetime
2016-11-09T00:58:12-08:00
documentation
PROPIPE
is_lateral_inspection
false