Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2016, 10:33 AM
  • 02 1642_02 1641_09112016_023408.mp4

Date
11/09/2016
W/O
602593
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00235
PipeID
P04076
Time
2:33 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3820
Sewer Name
02 ATLANTIC AVENUE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_602593_TV02018_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1641
Downstream MH
02 1642
Dir. of Survey
Upstream
Length Surveyed
261.8 ft.
Total Length
261.8 ft.
Structural Index
3
Structural Quick
3E21
Structural Rating
98
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
98
Pipe schematic from manhole 02 1641 to 02 1642
MH: 02 1641MH: 02 1642upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 16420.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish64.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start163.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.1 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES221.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES239.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.8 ft. MWM - Water Mark, 5 %of cross sectional area261.8 ft. AMH - Downstream Manhole, Survey Begins - 02 1641261.8 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (3)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    40.6 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    72.7 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    105.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
40.6CL
261.7CM
0MWM
105.7CM
261.8AMH02 1642
98.2TF
182.9TF
0AMH02 1641
128.4TF
197.2TF
22.3TF
72.7CM
0MWL

Properties (6)

additional_info
SC304569
custom_field_two
3
customer
LACSD
datetime
2016-11-09T02:33:45-08:00
documentation
PROPIPE
is_lateral_inspection
false