Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2016, 07:23 AM
  • 02 1632_02 1631_09112016_232500.mp4

Date
11/09/2016
W/O
602593
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00235
PipeID
P04069
Time
11:23 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3821
Sewer Name
02 ATLANTIC AVENUE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_602593_TV02018_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1631
Downstream MH
02 1632
Dir. of Survey
Upstream
Length Surveyed
213.9 ft.
Total Length
214 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
126
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
128
Pipe schematic from manhole 02 1631 to 02 1632
MH: 02 1631MH: 02 1632upstream0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 02 16322.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"53.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"103.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"103.9 ft. RFC - Roots Fine Connection, at 12 o'clock110.9 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: NO111 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"209.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start214 ft. AMH - Downstream Manhole, Survey Begins - 02 1631214 ft. MWM - Water Mark, 20 %of cross sectional area214 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 12 o'clock, within 8 inches of joint: NO

    103.1 ft. - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: NO

  • Roots Fine Connection, at 12 o'clock

    110.1 ft. - Roots Fine Connection, at 12 o'clock

Observations (12)

DistanceCodeObservation
0AMH02 1631
110.1TFA
214CM
103.1RFJ
0MWM
110.1RFC
160.8TFA
103TFA
211.3TF
214AMH02 1632
4.1CM
0MWL

Properties (6)

additional_info
SC304570
custom_field_two
3
customer
LACSD
datetime
2016-11-09T23:23:40-08:00
documentation
PROPIPE
is_lateral_inspection
false