Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2016, 09:09 AM
  • D 0165_D 0164_20160202_025739_.mp4

Date
02/02/2016
W/O
552384
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00157
PipeID
P10041
Time
1:09 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3132
Sewer Name
D JOINT OUTFALL D - UNIT 6 RELIEF
City
HAWTHORNE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_552384_TV05145_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
39 in.
Upstream MH
D 0165
Downstream MH
D 0164
Dir. of Survey
Downstream
Length Surveyed
625.5 ft.
Total Length
625.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2X00
O&M Rating
248
Overall Index
2
Overall Quick
Overall Rating
248
Pipe schematic from manhole D 0165 to D 0164
MH: D 0165MH: D 0164downstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 01650 ft. MWM - Water Mark, 45 %of cross sectional area2 ft. MGO - General Observation - MAGNESIUM H.O. START7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start624.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish625.5 ft. MSA - Survey Abandoned - FLOW NOT STRONG ENOUGH TO PULL BOAT THROUGH PIPE SECTION

Observation photos (1)

  • Water Mark, 45 %of cross sectional area

    0 ft. - Water Mark, 45 %of cross sectional area

Observations (8)

DistanceCodeObservation
2MGOMAGNESIUM H.O. START
0MGOLATERAL AT MH 9 OCLOCK
0MWL
7DAGS
0AMHD 0165
625.5MSAFLOW NOT STRONG ENOUGH TO PULL BOAT THROUGH PIPE SECTION
0MWM
624.9DAGS

Properties (7)

additional_info
SC225519
custom_field_two
5
customer
LACSD
datetime
2016-02-02T01:09:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
19820204