Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2016, 07:59 AM
  • H 0618_H 0617_20160216_235811.mp4

Date
02/16/2016
W/O
552365
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00191
PipeID
P11036
Time
11:59 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3149
Sewer Name
H JOINT OUTFALL H - UNIT 8H
City
BALDWIN PARK, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_552365_TV15175_FEB2016
Sewer Type
SIPHON
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
H 0618
Downstream MH
H 0617
Dir. of Survey
Downstream
Length Surveyed
470.1 ft.
Total Length
470.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2R00
O&M Rating
186
Overall Index
2
Overall Quick
Overall Rating
186
Pipe schematic from manhole H 0618 to H 0617
MH: H 0618MH: H 0617downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 06180 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area1.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAGNESIUM H.O. START148.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"358.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"466 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish470.1 ft. AMH - Downstream Manhole, Survey Ends - H 0617

Observation photos (2)

  • General Observation - MAGNESIUM H.O. START

    2 ft. - General Observation - MAGNESIUM H.O. START

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    466 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (9)

DistanceCodeObservation
148.1TFA
2MGOMAGNESIUM H.O. START
1.3DAGS
358.7TFA
0AMHH 0618
470.1AMHH 0617
0MWL
0MWM
466DAGS

Properties (6)

additional_info
SC225536
custom_field_two
4
customer
LACSD
datetime
2016-02-16T23:59:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false