Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2016, 06:55 AM
  • H 0619A_H 0604_20160216_225427.mp4

Date
02/16/2016
W/O
552365
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00191
PipeID
P11039
Time
10:55 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3149
Sewer Name
H JOINT OUTFALL H - UNIT 8H
City
WEST COVINA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_552365_TV15175_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
H 0619A
Downstream MH
H 0604
Dir. of Survey
Downstream
Length Surveyed
104 ft.
Total Length
104 ft.
Structural Index
1
Structural Quick
1C00
Structural Rating
20
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
1
Overall Quick
Overall Rating
24
Pipe schematic from manhole H 0619A to H 0604
MH: H 0619AMH: H 0604downstream0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 0619A0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - MAGNESIUM H.O. START4 ft. SRI - Surface Roughness Increased, from 09 to 03 o'clock, within 8 inches of joint: YES, Start26.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"50.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"74.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"104 ft. SRI - Surface Roughness Increased, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish104 ft. AMH - Downstream Manhole, Survey Ends - H 0604

Observation photos (2)

  • Surface Roughness Increased, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Roughness Increased, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    50.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

Observations (10)

DistanceCodeObservation
0MWL
4SRI
104SRI
50.7TFC
74.2TFC
26.4TFC
0AMHH 0619A
104AMHH 0604
2MGOMAGNESIUM H.O. START
0MWM

Properties (6)

additional_info
SC225536
custom_field_two
3
customer
LACSD
datetime
2016-02-16T22:55:26-08:00
documentation
PRO-PIPE
is_lateral_inspection
false