Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 25, 2016, 07:15 AM
  • 04 0072_04 0071_24022016_231610.mp4

Date
02/24/2016
W/O
552531
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11808
Time
11:15 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3267
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
WO_552531_TV04009_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
15 in.
Upstream MH
04 0072
Downstream MH
04 0071
Dir. of Survey
Downstream
Length Surveyed
273 ft.
Total Length
273 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 04 0072 to 04 0071
MH: 04 0072MH: 04 0071downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04 00720 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE24 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES34.9 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES36.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"57.5 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OFFSET98.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"99.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"133.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.5 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES140.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"172.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"181.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"211.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"219.8 ft. MGP - General Photograph - HOLE219.8 ft. H - Hole, from 09 to 12 o'clock, within 8 inches of joint: NO221.3 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS237.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"260.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"273 ft. AMH - Downstream Manhole, Survey Ends - 04 0071273 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (10)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    24 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    34.9 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OFFSET

    57.5 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OFFSET

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    140.5 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • General Photograph - HOLE

    219.8 ft. - General Photograph - HOLE

  • Hole, from 09 to 12 o'clock, within 8 inches of joint: NO

    219.8 ft. - Hole, from 09 to 12 o'clock, within 8 inches of joint: NO

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    221.3 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    237.5 ft. - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - COCKROACHES IN MANHOLE

    273 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (23)

DistanceCodeObservation
0MWM
219.8MGPHOLE
0AMH04 0072
237.5TFA
273AMH04 0071
0MWL
99.2TFA
221.3TFDROOTS
98.2TFA
273MGOCOCKROACHES IN MANHOLE
57.5TFDOFFSET
140.5CM
219.8H
140.9TF
34.9CM
181.4TFA
24CL
133.2TFC
36.7TFC
172.3TFC
260.5TFC
211.7TFC
0MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC225490
custom_field_two
2
customer
LACSD
datetime
2016-02-24T23:15:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false