Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2015, 10:30 AM
  • 08 0507_08 0506_20151207_033446.mp4

Date
12/07/2015
W/O
531054
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00021
PipeID
P00568
Time
2:30 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2925
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0507
Downstream MH
08 0506
Dir. of Survey
Downstream
Length Surveyed
354.1 ft.
Total Length
354.1 ft.
Structural Index
3
Structural Quick
4339
Structural Rating
39
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
40
Pipe schematic from manhole 08 0507 to 08 0506
MH: 08 0507MH: 08 0506downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O' CLOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O' CLOCK0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 05070 ft. MWM - Water Mark, 45 %of cross sectional area61.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"136.1 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES140.1 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES174.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"228 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO253 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start281.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"284.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 66"298.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish336.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"339.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"354.1 ft. VC - Vermin Cockroach354.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0506354.1 ft. MGO - General Observation - CONNECTION AT THE MH 5 O' CLOCK

Observations (25)

DistanceCodeObservation
354.1VC
284.8TFC
281.6TFC
354.1AMH08 0506
174.3TFC
0MGOCONNECTION AT THE MH 9 O' CLOCK
136.1FM
245.5FM
140.1FM
122.5TFC
64.6TFC
339.8TFC
298.2FL
224.7TFC
253FL
0MGOCONNECTION AT THE MH 3 O' CLOCK
0MWL
0AMH08 0507
354.1MGOCONNECTION AT THE MH 5 O' CLOCK
336.1TFC
228TFC
61.5TFC
177.8TFC
119.2TFC
0MWM

Properties (6)

additional_info
SC207026
custom_field_two
2
customer
LACSD
datetime
2015-12-07T02:30:45-08:00
documentation
PRO-PIPE
is_lateral_inspection
false