Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2015, 11:28 AM
  • 08 0522_08 0521_20151201_034038.mp4

Date
12/01/2015
W/O
531054
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00021
PipeID
P00584
Time
3:28 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2920
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0522
Downstream MH
08 0521
Dir. of Survey
Downstream
Length Surveyed
251.2 ft.
Total Length
251.2 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
412I
O&M Rating
104
Overall Index
2
Overall Quick
Overall Rating
113
Pipe schematic from manhole 08 0522 to 08 0521
MH: 08 0522MH: 08 0521downstream0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 05222 ft. OBZ - Obstacles Other, 5 %of cross sectional area, from 02 to 05 o'clock - DEBRIS2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start86.2 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES110.8 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES118.6 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES248.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish251.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0521251.2 ft. MGO - General Observation - CONNECTION AT THE MH 2 O' CLOCK251.2 ft. MGO - General Observation - CONNECTION AT THE MH 8 O' CLOCK

Observation photos (4)

  • Obstacles Other, 5 %of cross sectional area, from 02 to 05 o'clock - DEBRIS

    2 ft. - Obstacles Other, 5 %of cross sectional area, from 02 to 05 o'clock - DEBRIS

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    86.2 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    110.8 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    118.6 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
118.6CM
0MWM
248.3DAGS
0MWL
0AMH08 0522
251.2AMH08 0521
2OBZDEBRIS
251.2MGOCONNECTION AT THE MH 2 O' CLOCK
251.2MGOCONNECTION AT THE MH 8 O' CLOCK
86.2CM
110.8CM
2DAGS

Properties (6)

additional_info
SC207018
custom_field_two
3
customer
LACSD
datetime
2015-12-01T03:28:09-08:00
documentation
PRO-PIPE
is_lateral_inspection
false