Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2015, 07:08 AM
  • 08 0513_08 0512A_20151102_231906.mp4

Date
11/02/2015
W/O
531054
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00021
PipeID
P00575
Time
11:08 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2545
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0513
Downstream MH
08 0512A
Dir. of Survey
Downstream
Length Surveyed
201 ft.
Total Length
201 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 08 0513 to 08 0512A
MH: 08 0513MH: 08 0512Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 0513 (2304)0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area5.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start41.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"94.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"143.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"192.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"201 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish201 ft. AMH - Downstream Manhole, Survey Ends - 08 0512A (2315)

Observations (10)

DistanceCodeObservation
0AMH08 0513 (2304)
0MWM
192.1TFC
41.6TFC
94.8TFC
201DAGS
0MWL
143.8TFC
5.5DAGS
201AMH08 0512A (2315)

Properties (6)

additional_info
SC205609
custom_field_two
4
customer
LACSD
datetime
2015-11-02T23:08:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false