Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2016, 08:47 PM
  • 08 0502_08 0501A_20160111_130439.mp4

Date
01/11/2016
W/O
531054
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00021
PipeID
P25008
Time
12:47 PM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2292
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0501A
Downstream MH
08 0502
Dir. of Survey
Upstream
Length Surveyed
152.4 ft.
Total Length
152.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 08 0501A to 08 0502
MH: 08 0501AMH: 08 0502upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 13021 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish5.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"54.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"72.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start108.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"146.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start152.4 ft. MWM - Water Mark, 15 %of cross sectional area152.4 ft. AMH - Downstream Manhole, Survey Begins - 1251152.4 ft. MWL - Water Level, 10 %of cross sectional area

Observations (11)

DistanceCodeObservation
43.6TFC
0MWM
0AMH1251
98TFC
146.7TFA
152.4DAGS
0MWL
6DAGS
79.7DAE
152.4AMH1302
151.4DAE

Properties (6)

additional_info
SC225351
custom_field_two
4
customer
LACSD
datetime
2016-01-11T12:47:06-08:00
documentation
PRO-PIPE
is_lateral_inspection
false