Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2015, 07:53 AM
  • 08 0533_08 0532_20151104_000852.mp4

Date
11/03/2015
W/O
531054
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00021
PipeID
P00595
Time
11:53 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2546
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0533
Downstream MH
08 0532
Dir. of Survey
Downstream
Length Surveyed
243.4 ft.
Total Length
243.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 08 0533 to 08 0532
MH: 08 0533MH: 08 0532downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 0533 (2354)0 ft. MWM - Water Mark, 30 %of cross sectional area2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start149.3 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES230.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES240 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish243.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0532 (0008)

Observation photos (1)

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    149.3 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0MWL
149.3FL
0AMH08 0533 (2354)
0MWM
243.4AMH08 0532 (0008)
240DAGS
230.1CM
2.5DAGS

Properties (6)

additional_info
SC205610
custom_field_two
3
customer
LACSD
datetime
2015-11-03T23:53:49-08:00
documentation
PRO-PIPE
is_lateral_inspection
false