Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2015, 10:10 AM
  • 08 0519_08 0518_20151201_021945.mp4

Date
12/01/2015
W/O
531054
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00021
PipeID
P00581
Time
2:10 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2920
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0519
Downstream MH
08 0518
Dir. of Survey
Downstream
Length Surveyed
161.6 ft.
Total Length
161.6 ft.
Structural Index
4
Structural Quick
4331
Structural Rating
15
O&M Index
2
O&M Quick
412E
O&M Rating
68
Overall Index
2
Overall Quick
Overall Rating
83
Pipe schematic from manhole 08 0519 to 08 0518
MH: 08 0519MH: 08 0518downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 05190 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start12.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES37.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES45.1 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES104.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES161.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish161.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0518161.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 O' CLOCK

Observation photos (4)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    12.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    37.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    45.1 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    104.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MWM
0AMH08 0519
161.6DAGS
45.1CM
12.8FM
37.2FM
0MWL
161.6AMH08 0518
161.6MGOCONNECTION AT THE MH 9 O' CLOCK
2DAGS
104.5FM

Properties (6)

additional_info
SC207018
custom_field_two
2
customer
LACSD
datetime
2015-12-01T02:10:22-08:00
documentation
PRO-PIPE
is_lateral_inspection
false