Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 07:38 AM
  • 08 0492_08 0048_20151105_235421.mp4

Date
11/05/2015
W/O
531054
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00021
PipeID
P00550
Time
11:38 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2549
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0492
Downstream MH
08 0048
Dir. of Survey
Downstream
Length Surveyed
296.8 ft.
Total Length
296.8 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
124
Pipe schematic from manhole 08 0492 to 08 0048
MH: 08 0492MH: 08 0048downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 0492 (2339)0 ft. MWM - Water Mark, 20 %of cross sectional area2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start48.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"51.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"98.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"101.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"137.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES149.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"152.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"198.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES200.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"290.9 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES295 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish296.8 ft. AMH - Downstream Manhole, Survey Ends - 08 0048 (2354)296.8 ft. MGO - General Observation - LATERAL AT MH 12 OCLOCK

Observations (17)

DistanceCodeObservation
51.2TFC
2.9DAGS
295DAGS
137.9CM
290.9CM
296.8AMH08 0048 (2354)
296.8MGOLATERAL AT MH 12 OCLOCK
149.5TFC
48.5TFC
0MWL
152.1TFC
198.5CL
0AMH08 0492 (2339)
98.9TFC
200.2TFC
0MWM
101.7TFC

Properties (6)

additional_info
SC205617
custom_field_two
3
customer
LACSD
datetime
2015-11-05T23:38:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false