Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 07:03 AM
  • 08 0493A_08 0493_20151105_231905.mp4

Date
11/05/2015
W/O
531054
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00021
PipeID
P00552
Time
11:03 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2549
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0493A
Downstream MH
08 0493
Dir. of Survey
Downstream
Length Surveyed
275.4 ft.
Total Length
275.4 ft.
Structural Index
3
Structural Quick
3E21
Structural Rating
92
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
200
Pipe schematic from manhole 08 0493A to 08 0493
MH: 08 0493AMH: 08 0493downstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 0493A (2304)0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start71.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"74.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"121.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"125.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"160.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"170.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"218 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"221.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"264 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"264 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES266.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"273 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish275.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0493 (2318)

Observations (20)

DistanceCodeObservation
74.7TFC
221.7TFC
218TFC
170.6TFC
160.1CM
121.8TFC
264TFC
266.9TFC
275.4AMH08 0493 (2318)
264CL
273DAGS
10.7CM
71.9TFC
167.4TFC
0MGOLATERAL AT MH 9 OCLOCK
0MWM
125.1TFC
0AMH08 0493A (2304)
0MWL
2DAGS

Properties (6)

additional_info
SC205617
custom_field_two
3
customer
LACSD
datetime
2015-11-05T23:03:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false