Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2015, 08:11 AM
  • 08 0532_08 0531_20151104_002401.mp4

Date
11/04/2015
W/O
531054
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00021
PipeID
P00594
Time
12:11 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2546
Sewer Name
08 VICTORIA STREET TRUNK
City
CARSON, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_531054_TV08032_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0532
Downstream MH
08 0531
Dir. of Survey
Downstream
Length Surveyed
197.7 ft.
Total Length
197.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 08 0532 to 08 0531
MH: 08 0532MH: 08 0531downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 0532 (0012)0 ft. MWM - Water Mark, 30 %of cross sectional area4.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start163.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish195.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish197.7 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK197.7 ft. AMH - Downstream Manhole, Survey Ends - 08 0531 (0023)197.7 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK

Observations (10)

DistanceCodeObservation
0MWL
0AMH08 0532 (0012)
4.1DAGS
27.1CM
197.7MGOLATERAL AT MH 9 OCLOCK
163.8CM
0MWM
197.7AMH08 0531 (0023)
195.9DAGS
197.7MGOLATERAL AT MH 9 OCLOCK

Properties (6)

additional_info
SC205610
custom_field_two
3
customer
LACSD
datetime
2015-11-04T00:11:46-08:00
documentation
PRO-PIPE
is_lateral_inspection
false