Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2015, 09:00 AM
  • 14 0182_14 0181_20151113_011116.mp4

Date
11/13/2015
W/O
525225
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18221
Time
1:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2829
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
08
Purpose
Routine Assessment
Project
WO_525225_TV14034_SEPT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
14 0182
Downstream MH
14 0181
Dir. of Survey
Downstream
Length Surveyed
251 ft.
Total Length
251 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
412I
O&M Rating
104
Overall Index
2
Overall Quick
Overall Rating
107
Pipe schematic from manhole 14 0182 to 14 0181
MH: 14 0182MH: 14 0181downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01822 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start38.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"44.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES85.9 ft. TBC - Tap Break-In Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"137.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"188.9 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"235.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"249.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish251 ft. AMH - Downstream Manhole, Survey Ends - 14 0181251 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

Observations (13)

DistanceCodeObservation
0MWM
137.9TFC
249.1DAGS
44.3CM
235.7TFC
85.9TBC
0MWL
251AMH14 0181
38.6TF
251MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2DAGS
188.9TFA
0AMH14 0182

Properties (6)

additional_info
SC204163
custom_field_two
3
customer
LACSD
datetime
2015-11-13T01:00:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false