Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2015, 07:18 AM
  • 14 0188_14 0187_20151112_232919.mp4

Date
11/12/2015
W/O
525225
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18227
Time
11:18 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2829
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
08
Purpose
Routine Assessment
Project
WO_525225_TV14034_SEPT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
14 0188
Downstream MH
14 0187
Dir. of Survey
Downstream
Length Surveyed
325.3 ft.
Total Length
325.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
132
Pipe schematic from manhole 14 0188 to 14 0187
MH: 14 0188MH: 14 0187downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01882 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"98.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES99 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"174.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES175.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"251.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"322.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish325.3 ft. AMH - Downstream Manhole, Survey Ends - 14 0187

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES

    98.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
322.5DAGS
98.7DAGS
251.7TFC
0MWM
0MWL
175.7TFA
2DAGS
325.3AMH14 0187
174.1DAGS
99TFA
23.5TFC
0AMH14 0188

Properties (6)

additional_info
SC204163
custom_field_two
4
customer
LACSD
datetime
2015-11-12T23:18:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false