Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2015, 07:07 AM
  • 14 0189_14 0188_20151112_231821.mp4

Date
11/12/2015
W/O
525225
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18228
Time
11:07 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2829
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
08
Purpose
Routine Assessment
Project
WO_525225_TV14034_SEPT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
14 0189
Downstream MH
14 0188
Dir. of Survey
Downstream
Length Surveyed
328.6 ft.
Total Length
328.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
135
Pipe schematic from manhole 14 0189 to 14 0188
MH: 14 0189MH: 14 0188downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 01890 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start52.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"127.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES128.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"200.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"230.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES280.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"327 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.6 ft. AMH - Downstream Manhole, Survey Ends - 14 0188

Observations (12)

DistanceCodeObservation
2DAGS
230.9CM
0AMH14 0189
327DAGS
0MWM
127.4DAGS
280.7TFC
328.6AMH14 0188
52.7TFC
128.3TFA
200.2TFC
0MWL

Properties (6)

additional_info
SC204163
custom_field_two
3
customer
LACSD
datetime
2015-11-12T23:07:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false