Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2015, 06:49 AM
  • 14 0190_14 0189_20151112_230742.mp4

Date
11/12/2015
W/O
525225
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18229
Time
10:49 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2829
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
08
Purpose
Routine Assessment
Project
WO_525225_TV14034_SEPT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
14 0190
Downstream MH
14 0189
Dir. of Survey
Downstream
Length Surveyed
217.1 ft.
Total Length
217.1 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
117
O&M Index
2
O&M Quick
2O00
O&M Rating
162
Overall Index
2
Overall Quick
Overall Rating
279
Pipe schematic from manhole 14 0190 to 14 0189
MH: 14 0190MH: 14 0189downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 14 01900 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start23.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES27.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"201.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"216.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish216.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish216.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish217.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0189

Observations (15)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
23.9DAE
216.2DAGS
0AMH14 0190
201.6TF
0MWL
216.2CM
217.1AMH14 0189
2DAGS
216.2DAE
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWM
27.7CM
23.9CM
89.7TFA

Properties (6)

additional_info
SC204163
custom_field_two
3
customer
LACSD
datetime
2015-11-12T22:49:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false