Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2021, 10:59 AM
  • 01 0017_01 0016_04192021_041455.mp4

Date
04/19/2021
W/O
886005
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00682
Time
3:59 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8734
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_886005_TV01245_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
01 0017
Downstream MH
01 0016
Dir. of Survey
Downstream
Length Surveyed
424.1 ft.
Total Length
424.1 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
252
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
252
Pipe schematic from manhole 01 0017 to 01 0016
MH: 01 0017MH: 01 0016downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 00170 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start258.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"383 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"424.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0016424.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    258.1 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    329.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    383 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 3 OC'LOCK
383TB
0MGOCONNECTION AT THE MH 9 OC'LOCK
424.1AMH01 0016
0AMH01 0017
424.1CM
329.6TB
0MWL
3.1CM
0MWM
258.1TB

Properties (7)

additional_info
630074041921002
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-04-19T03:59:06-07:00
documentation
PROPIPE
is_lateral_inspection
false